Here a general description is given of the Heat Sink (HS) modules. The specific modules for the different houses are slightly individual. Specific descriptions can be found here:

Scheme:

The first letter of the ID describes the genera type of the name:

  • S stands for signal
  • A stands for actuator
  • C stands for component

For more information about the naming concept of the ID, the this wiki page: Naming Concept

Nr.IDNameSignalsComment
1C_BV-HC_VLBall Valve Heating Circuit

2S_TM-HC_VL_bMTemperature Heating CircuitPT100
3A_MX-HCMixing Valve Heating CircuitDOsmall lever on the mixer valve (directly behind the motor) must be moved so that it is parallel to the bypass,




if it is not brought into this position, there will always be a small leakage flow trough the bypass
4A_PU-HCPump Heating Circuit(0-10V) / On/OffFlow controlled by controllable pump: SF1 and SF2









Standard pump in SF3 and SF4, only on/off
4aA_CV-HCControl Valve Heating Circuit0-10VFlow controlled by control valve instead of controllable pump: SF3 and SF4
5S_TM-HC_VL_aMTemperature Heating CircuitPT100
6A_V3-HC3-Way Valve Heating CircuitDO
7C_HX-HC_CC_1Heatexchanger Heating Circuit
max.: 30 kWth
8A_V3-CC3-Way Valve Cooling CircuitDO
9A_CV-CC_VL_HCControl Valvle Cooling Circuit0-10V
10C_Red-CC_VL_1Pressure Reducer Cooling Circuit
pressure: 1,5 bar
11C_BV-CC_VLBall Valve Cooling Circuit

12C_BV-HC_RLBall Valve Heating Circuit

14C_BV-FDBall Valve Fill / Draining

15C_EV-HCExpansion Vessel Heating Circuit

16C_PR-HCPresser Release Valve Heating Circuit

18S_TM-HC_RLTemperature Heating CircuitPT100
19C_HX-HC_CC_2Heatexchanger Heating Circuit
max.: 10 kWth
20C_BV-HW_VLBall Valve Hot Water

21S_TM-HW_VLTemperature Hot WaterPT100
22S_FW-HW_VLFlow Water Hot Water4-20 mA / Counter20 mA = 15 l/min
23C_HX-HW_CCHeatexchanger Hot Water
max.: 1 kWth
24A_CV-CC_VL_CKControl Valvle Cooling Circuit0-10V
25C_Red-CC_VL_2Pressure Reducer Cooling Circuit
pressure:
26C_BV-HW_CKBall Valve Hot Water

27S_TM-HW_CKTemperature Hot WaterPT100
28A_PU-HW_CKPump Hot Water0-10V / On/Offat the moment self regulating
29A_MV-HW_1Magnetic Valve Hot WaterDO
30A_MV-HW_2Magnetic Valve Hot WaterDO
31A_MV-HW_3Magnetic Valve Hot WaterDO
32S_TM-HW_RLTemperature Hot WaterPT100
33C_BV-HW_RLBall Valve Hot Water

34S_TM-CC_VLTemperature Cooling CircuitPT100
35C_NV-HW_1Needle Valve Hot Water
flow rate: 2 l/min
36C_NV-HW_2Needle Valve Hot Water
flow rate: 4 l/min
37C_NV-HW_3Needle Valve Hot Water
flow rate: 6 l/min
38C_Red-CC_VL_3Pressure Reducer Cooling Circuit
pressure:
39S_FW-HW_CKFlow Water Cooling Circuit4-20 mA / Counter20 mA = 5 l/min
40A_BV-CC_RLMagnetic Valve Cooling CircuitDO

S_TM-RoomRoom temperature of the house
Simulated value
41C_PR-THPressure Release Valve

42C_PR-TMPressure Release Valve

43C_PR-TLPressure Release Valve