This page refers to the condensing boiler installed at single family house 1. It has 14kW nominal power.

Parameter - configuration

The configuration of the parameters must be changed manually on-site at the device.

To do this you have to enter the Fachmannebene with the password "1111".

Be careful with changes!

As soon as you change some of these parameters at the device, the according parameter has eventually to be changed in the simulation models or the VeriStand-models!

Nr.NameUnitValue
HG01Schalthysterese Brenner°C12
HG02

untere Brennerleistung Wärmeerzeuger in %

(Gebläseansteuerung)

%1
HG03

obere Brennerleistung WW (Gebläseansteuerung)

maximale Brennerleistung Warmwasser in %

%100
HG04

obere Brennerleistung HZ (Gebläseansteuerung)

maximale Brennerleistung Heizung in %

%100
HG07

Nachlaufzeit Heizkreispumpen

Nachlaufzeit der Heizkreispumpe im Heizbetrieb

min1
HG08Kesselmaximaltemperatur HZ (gültig für Heizbetrieb) TV-max°C90
HG09Brennertaktsperre gültig für Heizbetriebmin1
HG10eBus-Adresse des Wärmeerzeugers-1
HG12Gasart-Nat. Gas
HG13

Funktion Eingang E1

Der Eingang E1 kann mit verschiedenen Funktionen belegt werden

-keine
HG14

Funktion Ausgang A1 (230VAC)

Der Ausgang A1 kann mit verschiedenen Funktionen belegt werden

-keine
HG15Speicherhysterese Schaltdifferenz bei Speichernachladung°C5
HG16Pumpenleistung HK minimal%15
HG17Pumpenleistung HK maximal%

100

HG19Nachlaufzeit SLP (Speicherladepumpe)min3
HG20max. Speicherladezeitmin120
HG21Kesselminimaltemperatur TK-min°C20
HG22Kesselmaximaltemperatur TK-max°C90
HG23Warmwassermaximaltemperatur°C65
HG25Kesselübertemperatur bei Speicherladung°C20
HG33Laufzeit Brennerhysteresemin3
HG34eBus Einspeisung-Auto
HG37Typ Pumpenregelung (Festwert / Linear / Spreizung)-Lin.
HG38Soll-Spreizung Pumpenregelung (Spreizung)°C20
HG39Zeit Softstartmin3
HG40Anlagenkonfiguration (siehe Unten)-51
HG41Drehzahl ZHP WW%65
HG42Hysterese Sammler°C5
HG43Absenkung IO Basiswert-0
HG44GPV Kennlinie Offset%28.5
HG45Abgaslängenanpassung%5
HG46Kesselübertemperatur Sammler°C6
HG60minimale Schalthysterese Brenner°C7


HG40 System constellation

HG40 determines the system constellation in which the boiler is used.

In the lab we usually use configuration 51 or 52.

Important! The according configuration also has to be selcted in the VeriStand-model!

Configuration 51: control by power setpoint in %

  • burner start by signal from external controller
  • internal pump active for above 2 V
  • no temperature control
  • Input E2:
    • 0-10 V signal by external controller
    • 0-2V is off
    • 2-10 V is burner power min to max (see HG02 and HG04)
  • automated power reduction when temperature is close to TK-max (HG22)
  • automated switch of at temperature TK-max (HG22)

Configuration 52: control by temperature setpoint in °C

  • burner start by signal from temperature controller
  • internal pump active for above 2 V
  • control of boiler temperature
  • Input E2:
    • 0-10 V signal by external controller
    • 0-2V is off
    • 2-10 V is setpoint for boiler temperature between TK-min and TK-max (see HG21 and HG022)
  • Keine Stichwörter

Kommentar

  1. Unbekannter Benutzer (ge79biy) sagt:

    • What are the constellation options among which is possible to select?
    • What is a constellation?
    • For configuration 51: Is the internal pump active when a voltage is greater than 2 V, or the pump has a consumption <2 V when active?
    • For Input E2/E1: It is not clear how to differentiate between the options since the 0-10 V covers the other two ranges (0-2 V) and (2-10 V).