This Wiki-page describes the heat transfer station (connection heat network) of house 1. In contrast to the parent page, which is generalized, this page shows specifically the module of house 1 as it is mounted, prepared and used in the lab at the moment. 

Differences to general CHN module description

Differences between the specific setting in CHN House 1 compared to the general description of a CHN module are:

  • different ball valves are automated (actuators) - this changes also the IDs
  • pump and control valve on the network side (for feed-in and consumption) are part of the high temperature level instead of the medium temperature level
  • only two temperature levels are prepared and used at the moment
  • additional ball valve (45)
  • flow meter (5) does not exist in lab, flow values are calculated at another module (DH grid emulator)

Scheme:


Components and Signals

For more information about the naming concept of the ID, the this wiki page: Naming Concept

Nr.IDNameSignalsComment
1C_BV-TG_TH_1Ball Valve Thermal Grid
in SFxyz
2C_BV-TG_TH_2Ball Valve Thermal Grid
in SFxyz
3A_BV-TG_TH_3Ball Valve Thermal Grid (automated)DOin SFxyz
4C_BV-TG_TH_4Ball Valve Thermal Grid
in SFxyz
5S_FW-TG_THFlow Water Thermal Grid
no sensor, calculated by the connected DH modules
6S_TM-TG_TH_1Temperature Thermal GridPT100
7S_TM-HC_TH_1Temperature Heating CircuitPT100
8C_BV-HC_TH_1Ball Valve Heating Circuit

9C_BV-TG_TM_1Ball Valve Thermal Grid
in SFxyz
10C_BV-TG_TM_2Ball Valve Thermal Grid
in SFxyz
11A_BV-TG_TM_3Ball Valve Thermal Grid (automated)DOin SFxyz
12A_BV-TG_TM_4Ball Valve Thermal Grid (automated)DOin SFxyz
13A_CV-TG_THControl Valvle Thermal Grid10V
14C_CV-TG_TMCheck Valve Thermal Grid

15A_PU-TG_THPump Thermal Grid0-10V & On/Offadditionally CHN-A_PU-TH must be true (on/off)
16S_TM-TG_TM_1Temperature Thermal GridPT100
17S_TM-TG_TM_2Temperature Thermal GridPT100
18S_TM-HC_TM_1Temperature Heating CircuitPT100
19S_FW-HC_TMFlow Water Heating CircuitMID
20A_PU-HC_TH_IMPPump Heating Circuit0-10V & On/Offadditionally CHN-A_PU-TH must be true (on/off)
21A_PU-HC_TH_EXPPump Heating Circuit0-10V & On/Offadditionally CHN-A_PU-TH must be true (on/off)
22A_BV-HC_TH_INBall Valve Heating CircuitDO
23A_BV-HC_TH_OUBall Valve Heating CircuitDO
24S_TM-HC_TM_2Temperature Heating CircuitPT100
25C_BV-HC_TLBall Valve Heating Circuit

26C_EV-TG_TMExpansion Vessel Thermal Grid

27C_SG-TG_TMSafety Group

28C_HX-TLHeatexchanger Low Temperature

29C_BV-TG_TL_1Ball Valve Thermal Grid
in SFxyz
30C_BV-TG_TL_2Ball Valve Thermal Grid
in SFxyz
31A_BV-TG_TL_3Ball Valve Thermal GridDOin SFxyz
32C_BV-TG_TL_4Ball Valve Thermal Grid
in SFxyz
33S_FW-TG_TLFlow Water Thermal Grid
no sensor, calculated by the connected DH modules
34A_CV-TG_TLControl Valvle Thermal Grid10V
35C_CV-TG_TLCheck Valve Thermal Grid

36A_PU-TG_TLPump Thermal Grid0-10V & On/Off
37S_TM-TG_TL_2Temperature Thermal GridPT100
38S_TM-HC_TL_2Temperature Heating CircuitPT100
39S_FW-HC_TLFlow Water Heating CircuitCounter
40A_PU-HC_TL_IMPPump Heating Circuit0-10V & On/Off
41A_PU-HC_TL_EXPPump Heating Circuit0-10V & On/Off
42A_BV-HC_TL_INBall Valve Heating CircuitDO
43A_BV-HC_TL_OUBall Valve Heating CircuitDO
44C_HX-THHeatexchanger High Temperature

46C_PR-TG_THPressure Release Valve

47C_PR-TG_TMPressure Release Valve

48C_PR-TG_TLPressure Release Valve

49C_BV-HC_TLBall Valve Heating Circuit

50C_BV-HC_TLBall Valve Heating Circuit

51C_PR-HC_TMPressure Release Valve



Data Sheets:

Ultra Sonic Flow Meter:

Control Valve:




Pumps:

Other Sensors:

see Heat Sink - Hardware

Pdf of the Scheme: 

COSES SF1 CHN.pdf



  • Keine Stichwörter

Kommentar

  1. Thomas Licklederer sagt:

    Daniel Zinsmeister Please have a look if this is correct and also a special look on the comments for the individual signals. (not urgent)