The first letter of the ID describes the genera type of the name:

  • S stands for signal
  • A stands for actuator
  • C stands for component

For more information about the naming concept of the ID, the this wiki page: Naming Concept

Nr.IDNameSignalsComment
1C_BV-PS_VL_1Ball Valve Producer Side

2S_TM-PS_VLTemperature Producer SidePT100
3S_TM-BT_1Temperature Thermal StoragePT100
4S_TM-BT_2Temperature Thermal StoragePT100
5S_TM-BT_3Temperature Thermal StoragePT100
6S_TM-BT_4Temperature Thermal StoragePT100
7S_TM-BT_5Temperature Thermal StoragePT100
8S_TM-BT_6Temperature Thermal StoragePT100
9S_TM-BT_7Temperature Thermal StoragePT100
10S_TM-BT_8Temperature Thermal StoragePT100
11S_TM-BT_9Temperature Thermal StoragePT100
12S_TM-BT_10Temperature Thermal StoragePT100
13S_TM-HC_VLTemperature Heating CircuitPT100
14C_BV-HC_VLBall Valve Heating Circuit
only open, if 37 is closed
15S_TM-HC_HW_VLTemperature Heating CircuitPT100
16C_BV-PS_RL_1Ball Valve Producer Side
only open, if 38 is closed
17S_TM-PS_RLTemperature Producer SidePT100
20S_TM-HC_RLTemperature Heating CircuitPT100
21C_BV-HC_RLBall Valve Heating Circuit

22A_PU-HC_RLPump Heating Circuit0-10V & On/Off
23S_FW-HC_HW_RLFlow Water Heating Circuit4-20 mA & Counter20 mA = 20 l/min
24S_TM-HC_HW_RLTemperature Heating CircuitPT100
25C_BV-HW_VLBall Valve Hot Water

26C_BV-HW_CKBall Valve Hot Water

27C_BV-HW_FWBall Valve Hot Water

28S_TM-BT_11Temperature Thermal StoragePT100
29S_TM-BT_12Temperature Thermal StoragePT100
30S_TM-BT_13Temperature Thermal StoragePT100
31S_TM-BT_14Temperature Thermal StoragePT100
32S_TM-HWS_1Temperature Hot Water StoragePT100
33S_TM-HWS_2Temperature Hot Water StoragePT100
34S_TM-HWS_3Temperature Hot Water StoragePT100
35C_FI-HCFilter Heating Circuit

37C_BV-PS_VL_2Ball Valve Producer Side
only open, if 14 is closed
38C_BV-PS_RL_2Ball Valve Producer Side
only open, if 16 is closed
39S_PW-BTPressure Water Inlet0-10V0-10V
40C_PR-BT_TH_1Pressure Release Valve

41C_PR-BT_TM_1Pressure Release Valve

42C_PR-BT_TM_2Pressure Release Valve

43C_BV-BT_TH_1 Ball Valve Hot Water

44C_BV-BT_TH_2Ball Valve Hot Water

45C_BV-BT_TM_1 Ball Valve Cold Water

46C_BV-BT_TM_2Ball Valve Cold Water

47C_BV-BT_TM_3Ball Valve Cold Water

48C_SG-TG_THSafety Group

49C_EV-TG_THExpansion Vessel Thermal Grid

50C_BV-BT_TH_2Ball Valve Hot Water

51C_EV-TG_TMExpansion Vessel Thermal Grid

Data Sheets:

Thermal Storage: SPU 2 - 800


Hot Water Storage: SEM 1 - 500l

other sensors:

see Heat Sink - Hardware

Pdf of the Scheme: 

COSES SF1 TS.pdf


  • Keine Stichwörter