Parameters in LabVIEW-model
These parameters have to be set before converting to a VeriStand-model.
Parameters in VeriStand (as inputs)
These parameters have to be set in the system definition file of VeriStand by setting the initial values of the according inputs.
| Nr. | parameter | value | unit | description | comment | 
|---|---|---|---|---|---|
| 1 | Control_Strategy | 0 | - | determines how the boiler is controlled by burner power - 0 by target boiler temperature - 1  | is coupled to the hardware parameter HG40 that describes the configuration | 
Parameters in VeriStand (as parameters)
These parameters are parameters of the VeriStand model control&safety.
| Nr. | parameter | value | unit | description | comment | 
|---|---|---|---|---|---|
| 1 | nominal_power[kW] | 14 | kW | nominal power of boiler | is taken as maximal power for control | 
| 2 | HG04_power_perc.max | 1 | - | maximal allowed percentage of nominal power | hardware parameter | 
| 3 | HG02_power_perc.min | 0,01 | - | minimal allowed percentage of nominal power | hardware parameter | 
| 4 | HG22_TK.max | 90 | °C | max. boiler temperature | hardware parameter, relevant for automatic modulation | 
| 5 | HG21_TK.min | 20 | °C | min. boiler temperature | hardware parameter | 
| 6 | Voltage_run.max | 10 | V | voltage that equals maximal percentage or max. temperature | for PID controller | 
| 7 | Voltage_run.min | 2 | V | voltage that equals minimal percentage or min. temperature | |
| 8 | Voltage_off.min | 0 | V | voltage that turns boiler off | |
| 9 | proportional gain (Kc)(12,1) | 0,3  | - | for power control | |
| 10 | integral time (Ti, min)(12,1) | 0,6 | - | for power control | |
| 11 | derivative time (Td, min)(12,1) | 0 | - | for power control | 
Parameters of / at the hardware.
These parameters have to be adjusted at the hardware itself. They can be found in the subsections of the hardware section.
The boiler parameter settings at the hardware can be found here.