Parameters in LabVIEW-model

These parameters have to be set before converting to a VeriStand-model.

Nr.parametervalueunitdescriptioncomment
none




Parameters in VeriStand

These parameters have to be set in the system definition file of VeriStand by setting the initial values.

Nr.parametervalueunitdescriptioncomment
1T_max_HWS70°Ctemperature in the domestic hot water storage that corresponds to SOC=100%in Conversion_SF1_64/ Inports/ ParametersSF1
2T_max_TS190°Ctemperature in the thermal storage that corresponds to SOC=100%in Conversion_SF1_64/ Inports/ ParametersSF1
3T_reference_HWS20°Ctemperature in the domestic hot water storage that corresponds to SOC=0%in Conversion_SF1_64/ Inports/ ParametersSF1
4T_reference_TS120°Ctemperature in the thermal storage that corresponds to SOC=0%in Conversion_SF1_64/ Inports/ ParametersSF1
5true_4_Sensors_false_100 (false)bool

determines weather the measurements of the 4 internal storage temperature sensors are taken for the calculation of the energy content of the storage or the 10 outer storage temperature sensors

true (1) - 4 inner sensors

false (0) - 10 outer sensors

in Conversion_SF1_64/ Inports/ ParametersSF1

Parameters of / at the hardware

These parameters have to be adjusted at the hardware itself. They can be found in the subsections of the hardware section.