Parameters in LabVIEW-model

These parameters have to be set before converting to a VeriStand-model.

Parameters in VeriStand (as inputs)

These parameters have to be set in the system definition file of VeriStand by setting the initial values of the according inputs.

Nr.parametervalueunitdescriptioncomment
1Control_Strategy0-

determines how the boiler is controlled

by burner power - 0

by target boiler temperature - 1

is coupled to the hardware parameter HG40 that describes the configuration

Parameters in VeriStand (as parameters)

Nr.parametervalueunitdescriptioncomment
1nominal_power[kW]20kWnominal power of boileris taken as maximal power for control
2HG04_power_perc.max1-maximal allowed percentage of nominal powerhardware parameter
3HG02_power_perc.min0,23-minimal allowed percentage of nominal powerhardware parameter
4HG22_TK.max90°Cmax. boiler temperaturehardware parameter, relevant for automatic modulation
5HG21_TK.min20°Cmin. boiler temperaturehardware parameter
6Voltage_run.max10Vvoltage that equals maximal percentage or max. temperaturefor PID controller
7Voltage_run.min2Vvoltage that equals minimal percentage or min. temperature
8Voltage_off.min0Vvoltage that turns boiler off
9proportional gain (Kc)(13,1)

0,3

-
for power control
10integral time (Ti, min)(13,1)0,6-
for power control
11derivative time (Td, min)(13,1)0,00-
for power control

Parameters of / at the hardware.

These parameters have to be adjusted at the hardware itself. They can be found in the subsections of the hardware section.

The boiler parameter settings at the hardware can be found here.