Scheme:

The first letter of the ID describes the genera type of the name:

  • S stands for signal
  • A stands for actuator
  • C stands for component

For more information about the naming concept of the ID, the this wiki page: Naming Concept

Nr.IDNameSignalsComment
1S_TM-CC_RLTemperature Cooling CircuitPT100
2A_MX-CCMixing Valve Cooling Circuit

DO


3S_TM-BC_TSTemperature Heat PumpPT100
4S_TM-BC_RL_bMTemperature Brine CircuitPT100
5A_MX-BCMixing Valve Brine CircuitDO
6S_FW-BCFlow Water Brine Circuit4-20mA & Counter20 mA = 35 l/min
7S_TM-BC_RL_aMTemperature Brine CircuitPT100
8C_BV-BC_RLBall Valve Brine Circuit

9C_BV-FDBall Valve Fill / Draining

10C_EV-BCExpansion Vessel Brine Circuit

11C_PR-BCPresser Release Valve Brine Circuit

12S_TM-BC_VLTemperature Brine CircuitPT100
13C_BV-BC_VLBall Valve Brine Circuit

14S_TM-HC_VLTemperature Heating CircuitPT100
15C_BV-HC_VLBall Valve Heating Circuit

16S_FW-HCFlow Water Heating Circuit4-20mA & Counter20 mA = 40 l/min
17S_TM-HC_RLTemperature Heating CircuitPT100
18C_BV-HC_RLBall Valve Heating Circuit

19A_EH-BCElectric Heater Brine Circuit0-10V



A.HPControl Signal Heat Pump0-10V

Configuration 51 at the WPM

0-1 V: HP off

1-5V: HP on

5-10V: Additional Electric Heater on (modulating)

SPFS_TM-WWTemperature signal of warm water for the heat pump

set to 66 °C (=1 kOhm)

Data Sheets:

Heat Pump (BWS 1-10)

Ground source - thermal storage (SE2-300)

Other sensors:

see Heat Sink