Scheme:
The first letter of the ID describes the genera type of the name:
- S stands for signal
- A stands for actuator
- C stands for component
For more information about the naming concept of the ID, the this wiki page: Naming Concept
Nr. | ID | Name | Signals | Comment |
---|---|---|---|---|
1 | S_TM-CC_RL | Temperature Cooling Circuit | PT100 | |
2 | A_MX-CC | Mixing Valve Cooling Circuit | DO | |
3 | S_TM-BC_TS | Temperature Heat Pump | PT100 | |
4 | S_TM-BC_RL_bM | Temperature Brine Circuit | PT100 | |
5 | A_MX-BC | Mixing Valve Brine Circuit | DO | |
6 | S_FW-BC | Flow Water Brine Circuit | 4-20mA & Counter | 20 mA = 35 l/min |
7 | S_TM-BC_RL_aM | Temperature Brine Circuit | PT100 | |
8 | C_BV-BC_RL | Ball Valve Brine Circuit | ||
9 | C_BV-FD | Ball Valve Fill / Draining | ||
10 | C_EV-BC | Expansion Vessel Brine Circuit | ||
11 | C_PR-BC | Presser Release Valve Brine Circuit | ||
12 | S_TM-BC_VL | Temperature Brine Circuit | PT100 | |
13 | C_BV-BC_VL | Ball Valve Brine Circuit | ||
14 | S_TM-HC_VL | Temperature Heating Circuit | PT100 | |
15 | C_BV-HC_VL | Ball Valve Heating Circuit | ||
16 | S_FW-HC | Flow Water Heating Circuit | 4-20mA & Counter | 20 mA = 40 l/min |
17 | S_TM-HC_RL | Temperature Heating Circuit | PT100 | |
18 | C_BV-HC_RL | Ball Valve Heating Circuit | ||
19 | A_EH-BC | Electric Heater Brine Circuit | 0-10V | |
A.HP | Control Signal Heat Pump | 0-10V | Configuration 51 at the WPM 0-1 V: HP off 1-5V: HP on 5-10V: Additional Electric Heater on (modulating) | |
SPF | S_TM-WW | Temperature signal of warm water for the heat pump | set to 66 °C (=1 kOhm) |
Data Sheets:
Heat Pump (BWS 1-10)
Ground source - thermal storage (SE2-300)
Other sensors:
see Heat Sink