Error Codes x xx xx

House x:

  • 1: SF1
  • 2: SF2
  • 3: SF3
  • 4: SF4
  • 5: MF5
  • 6: DH1-6
  • 7: DH7-12
  • 8: DH13-15

Module xx:

  • 01: General
  • 02: Heat Sink
  • 03: Thermal Storage
  • 04: Conn. Heat Network
  • 05: Booster Heat Pump
  • 06: CHP
  • 07: Stirling
  • 08: Condensing Boiler
  • 09: Solar Thermal
  • 10: GSHP
  • 11: ASHP
  • 12: Cold Sink
  • 61: DH1
  • 62: DH2
  • 63: DH3
  • 64: DH4
  • 65: DH5
  • 66: DH6
  • 67: DH7
  • 68: DH8
  • 69: DH9
  • 70: DH10
  • 71: DH11
  • 72: DH12
  • 73: DH13
  • 74: DH14
  • 75: DH15

Error Type xx:

  • 01: Output Signal Mapping Error
    Names or number of Outputs doesn't match => All signals of the house are set to 0
  • 02: Watchdog Count Error
    Watchdog doesn't count up => All signals of the house are set to 0
  • 03: Leakage
    Leakage detected => All signals of the house are set to 0
  • 11: Safety violation
    AO or DO signal is violating its Safety Check => Affected signal is set to 0
  • 12: Out of Range (0-10V)
    AO signal is <0V or >10V => Affected signal is set either to 0 or 10V
  • 13: 2 True signals
    2 True signals at one unit (e.g. open valve = close valve = true) => both signals are set false
  • 14: Minimum Down Time violation
    Minimum Down Time of the module is violated => Module safety overwrites, this error type is only for documenting
  • 15: Hydraulic Short Circuit
    Valves are operated so that a hydraulic short circuit is generated => Pump / Control valve signals are set to 0V
  • 16: Pump cannot operate
    Pump is either blocked by a valve or switched off => Affected signal is set to 0V
  • 17: Flow is blocked
    2 control valves are turned off => One valve gets turned on
  • 18: Humidifier off
    Steam Humidifier is switched off, but input signal >0
  • 19: Booster Heat Pump blocked
    Ball valves on grid or house side are closed => BHP_on signal is ignored
  • 20: Booster Heat Pump temperature violation
    Temperatures are too high / low
  • 21: Booster Heat Pump switched off
    BHP_on signal is "off", but BHP is requested
  • 22: Too many starts per hour
    Too many starts per hour, signal is set to 0
  • 23: Internal error from device
    Device has an internal error (e.g. because of too many starts)


99999 is the code for no error.