Scheme:
The first letter of the ID describes the genera type of the name:
- S stands for signal
- A stands for actuator
- C stands for component
For more information about the naming concept of the ID, the this wiki page: Naming Concept
| Nr. | ID | Name | Signals | Comment |
|---|---|---|---|---|
| 1 | S_TM-CC_RL | Temperature Cooling Circuit | PT100 | |
| 2 | A_MX-CC | Mixing Valve Cooling Circuit | DO | |
| 3 | S_TM-BC_TS | Temperature Heat Pump | PT100 | |
| 4 | S_TM-BC_RL_bM | Temperature Brine Circuit | PT100 | |
| 5 | A_MX-BC | Mixing Valve Brine Circuit | DO | |
| 6 | S_FW-BC | Flow Water Brine Circuit | 4-20mA & Counter | 20 mA = 35 l/min |
| 7 | S_TM-BC_RL_aM | Temperature Brine Circuit | PT100 | |
| 8 | C_BV-BC_RL | Ball Valve Brine Circuit | ||
| 9 | C_BV-FD | Ball Valve Fill / Draining | ||
| 10 | C_EV-BC | Expansion Vessel Brine Circuit | ||
| 11 | C_PR-BC | Presser Release Valve Brine Circuit | ||
| 12 | S_TM-BC_VL | Temperature Brine Circuit | PT100 | |
| 13 | C_BV-BC_VL | Ball Valve Brine Circuit | ||
| 14 | S_TM-HC_VL | Temperature Heating Circuit | PT100 | |
| 15 | C_BV-HC_VL | Ball Valve Heating Circuit | ||
| 16 | S_FW-HC | Flow Water Heating Circuit | 4-20mA & Counter | 20 mA = 40 l/min |
| 17 | S_TM-HC_RL | Temperature Heating Circuit | PT100 | |
| 18 | C_BV-HC_RL | Ball Valve Heating Circuit | ||
| 19 | A_EH-BC | Electric Heater Brine Circuit | 0-10V | |
| A.HP | Control Signal Heat Pump | 0-10V | Configuration 51 at the WPM 0-1 V: HP off 1-5V: HP on 5-10V: Additional Electric Heater on (modulating) | |
| SPF | S_TM-WW | Temperature signal of warm water for the heat pump | set to 66 °C (=1 kOhm) |
Data Sheets:
Heat Pump (BWS 1-10)
Ground source - thermal storage (SE2-300)
Other sensors:
see Heat Sink