CoolMUC-2
End of Life
After 9 years of operation the hardware of CoolMUC-2 can no longer offer reliable service. The system is targeted to be turned off latest Friday 13.12.2024. This will also affect all housing systems attached to CoolMUC-2. Due to network degradation we can only support single node jobs on a best-effort basis until then. In case of further hardware problems, the shutdown date might be much earlier.
Overview of CoolMUC-2 characteristics
Hardware | |
Number of nodes | 812 |
Cores per node | 28 |
Hyperthreads per core | 2 |
Core nominal frequency | 2.6 GHz |
Memory (DDR4) per node | 64 GB (Bandwidth 120 GB/s - STREAM) |
Bandwidth to interconnect per node | 13,64 GB/s (1 Link) |
Bisection bandwidth of interconnect (per island) | 3.5 TB/s |
Latency of interconnect | 2.3 µs |
Peak performance of system | 1400 TFlop/s |
Infrastructure | |
Electric power of fully loaded system | 290 kVA |
Percentage of waste heat to warm water | 97% |
Inlet temperature range for water cooling | 30 … 50 °C |
Temperature difference between outlet and inlet | 4 … 6 °C |
Software (OS and development environment) | |
Operating system | SLES15 SP1 Linux |
MPI | Intel MPI 2019, alternatively OpenMPI |
Compilers | Intel icc, icpc, ifort 2019 |
Performance libraries | MKL, TBB, IPP |
Tools for performance and correctness analysis | Intel Cluster Tools |